Procedure Detailed steps STE display
6 Set the occupied heating
setpoint.
This setpoint is used as the active setpoint when
the space is occupied.
1.
Press the or buttons to set the occupied
heating setpoint. The setpoint will change in
0.5° increments.
2.
Press the
button to save the setpoint and
advance to the next function.
Note: This setpoint can also be changed as
described in the section Changing the room
setpoint on page 23.
7 Set the unoccupied
cooling setpoint.
This setpoint is used as the active setpoint when
the space is unoccupied.
1.
Press the or buttons to set the
unoccupied cooling setpoint. The setpoint will
change in 0.5° increments.
2.
Press the
button to save the setpoint and
advance to the next function.
8 Set the unoccupied
heating setpoint.
This setpoint is used as the active setpoint when
the space is unoccupied.
1.
Press the or buttons to set the
unoccupied heating setpoint. The setpoint will
change in 0.5° increments.
2.
Press the
button to save the setpoint and
advance to the next function.
9 Set the supply air
temperature changeover
setpoint.
Not used in all models.
This setpoint sets the supply air temperature at
which the controller will change between heating
to cooling.
1.
Press the or buttons to set the
changeover setpoint. The setpoint will change
in 1° increments.
2.
Press the
button to save the setpoint and
advance to the next function.
Procedure to set the temperature setpoints (continued)
SimplyVAV Section 4: Configuring the controllers
Revision E 29