SSS-1000 Series 1 Installation Guide
Installation Guide
Differential Pressure Flow Sensors
SSS-1000 Series
Mounting
1. Determinetheduct’sowdirectionandinstall
thesensorbasedonthesensor’sowarrow
imprint.
NOTE: The sensor must be mounted with the
arrow pointing in the direction of the air
ow.
2. Cuta7/8"holeintheducttoacceptthesensor
probes.
3. Aachusingtwoself-tappingscrewsinsertedin
the3/16"mountingholes.
Connections
Connectionsuse3/8"(SSS-100x)orODpolyethylene
tubing.Checkthatthereareno sharp bends in the
tubingatanyconnection.Bendsandcreasesmay
leakastubingages.
1. ConnectthePort“H”tothe“High”inputonthe
VAVcontroller.
2. ConnectthePort“L”tothe“Low”inputontheVAV
controller.
NOTE: For using SSS-100x sensors with CSC-
3000 series, CSP-4000/5000 series,
KMD-7000 series, and BAC-7000 series
controllers, use a 3/8" to 1/4" barb union
adapter and appropriate polyethylene
tubing to the sensor and controller. For
maximum accuracy in the CSP-5000 series,
KMD-7000 series, and BAC-7000 series
controllers, the 3/8" OD tubing between the
sensor and the adapter should be as short as
possible, and the 1/4" OD tubing from the
adapter to the controller should be 24" long
(on both the High and the Low sides). OR
use the equivalent SSS-101x sensor.
Mounting 1
Connections 1
Select Specifications 2
Maintenance 2
More Information 2
Important Notices 2
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - Installation Guide

SSS-1000 Series 1 Installation GuideInstallation GuideDifferential Pressure Flow SensorsSSS-1000 Series Mounting1. Determinetheduct’sowdirect

Seite 2 - More Information

SSS-1000 Series 2 Installation Guide© 2014 KMC Controls, Inc. 655-019-01LKMC Controls, Inc.19476IndustrialDriveNewParis,IN46553574.831.5250w

Kommentare zu diesen Handbüchern

Keine Kommentare