KMC Controls
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www. kmccontrols.com
016-019-01
Adjustments and Calibration
DANGER
The MCP-1160 contains a large powerful spring.
Exercise extreme caution if disassembly is required.
The actuator shaft MUST be restrained to prevent
the spring from expanding.
The MCP-1160 contains an 8-13 psi spring. A
positioner allows the unit to operate over any 5 psi
span with the start-point adjustable from 3-10 psi.
Replace the 5 psi spring with a 10 psi spring to widen
the span.
To change the positioner start-point:
1. Apply the desired signal pressure
2. Rotate the start-point adjuster until the actuator
starts to stroke.
Maintenance
The MCP-1160 actuator is designed for long term
reliability. No routine maintenance is required,
however care should be taken during any installation
or maintenance due to the power of the actuator.
Kommentare zu diesen Handbüchern